| 1.2 Cellls of series ÊÑÎ-386Ì, KCO-396, KC0-397 |
|
Factory-assembled switch-gear cells of one-sided maintenance with air insulation, enclosed in a metal jacket; the cells comprise permanently mounted switching devices rated at the voltage of 6 and 10 kV and are intended for operation in switch-gears of three-phase alternating current systems with the frequency of 50 Hz and with an insulated or grounded neutral.
The cells are manufactured on the basis of welded structures. Rated values of operating parameters, design and circuit network make it possible to reach an optimum in implementing tasks in compliance with customers' requirements.
with load-breaking isolator
with load-breaking isolator and fuses
with isolators
sectionalizing switch
with load-breaking isolator and current transformers
busbar bridges
with lightning arresters
voltage transformer and other designs according to request
frame consisting of units of sheet metal and sections assembled with the use of welded joints and bolted connections
door made of sheet metal with a central lock
the door of the cell is fitted with a peephole protected by safety glass
high reliability at the expense of using standardized components and apparatus
cells have been tested in compliance with the state standards (GOST 14694 and GOST 1516.1)
all switching operations are conducted with the external door closed
spacious compartment of cable connections
availability of functional interlocking devices
Climatic design of cells KCO ÓÇ; ÓÕË according to GOST 15150.
Cells KCO are mostly designed for installation indoors with draught ventilation and without artificial regulation of climatic conditions.
The maintenance environment should be explosion-proof, should not contain aggressive gases, vapors and chemical deposits, should be free of current-conducting dust and saturated vapor.
| Parameters |
Values |
|
Rated voltage, kV
|
6; 10 |
|
Maximum operating voltage, kV
|
7,2; 12 |
|
Rated current of main circuits, A
|
630 |
|
Interrupting current rating of fuses, kA
|
31,5 |
|
Fuses interrupting current rating
|
|
|
at Un = 6 kV
|
50-80-100-120 |
|
at Un = 10 kV
|
31,5-40-63-80 |
|
Type of maintenance
|
one-sided |
|
Degree of protection at the cell facade
|
IP 40 |
|
Overall dimensions, mm
|
800x800x1900 |
|
load-breaking isolator of BHÏÁ-10 type (spring drive)
load-breaking isolator of BHÏ-M type
isolator
grounding isolator
voltage transformers
fuses
| Parameters |
Values |
|
Rated voltage, kV
|
6; 10 |
|
Maximum operating voltage, kV
|
6,9; 11,5 |
|
Rated current of main circuits, A
|
200; 400; 630 |
|
Rated current of collected buses, A
|
400; 630 |
|
Type of maintenance
|
one-sided |
|
Degree of protection at the cell facade
|
IP 40 |
|
Overall dimensions, mm
|
1000x1000x2080 |
|
load-breaking isolator of BHÏÁ-10 type (spring drive)
load-breaking isolator of BHP-10 type
isolator
grounding isolator
voltage transformers
fuses
| Parameters |
Values |
|
Rated voltage, kV
|
6; 10 |
|
Maximum operation voltage, kV
|
7,2; 12 |
|
Rated current of main circuits, A
|
630; 1000 |
|
Interrupting current rating, kA
|
20:31,5 |
|
Type of maintenance
|
one-sided |
|
Degree of protection at the cell facade
|
IP 40 |
|
Overall dimensions
|
800x800x1900 |
|
load-breaking isolator, type of NAL, NALF, OK, OKD (manufactured by ABB EJF company, a.s.)
isolator
grounding isolator
voltage transformers
fuses
|