9. Load-breaking isolator with grounding blades of ÂÍÏÁ-10-630(400) type

General data

Hard-gas AC load-breaking isolator with grounding blades, type ÂÍÏÁ-10-630(400)/20 is intended for closing and opening energized sections of three-phase AC circuits of commercial frequency of 50 Hz and voltage rated at 10 kV. The isolators are mounted as completing items in package switch-gears (factory-assembled switch-gears), one-sided maintenance cells (KCO), package transformer substations and also for replacing load-breaking isolators of obsolete designs being currently in service.

Brief specifications

Parameters Values

Rated voltage, kV

6-10

Maximum working voltage, kV

12

Rated current of main circuits, A

400; 630

Switch interrupting current rating, kA

20

Rated current of electrodynamic stability, kA

51

Mass, kg

29

Overall dimensions, mm

390x528x535

Operation conditions

ambient air temperature: from - 400C to +400C
altitude above sea level: not exceeding 1000 m
working environment: explosion-proof

Previous Index Photoalbum Next
  Copyright © 2001 JSC "Kushva Electromechanical Plant" 419473   

. .