| 9. Load-breaking isolator with grounding blades
of ÂÍÏÁ-10-630(400) type
|
|
Hard-gas AC load-breaking isolator with grounding blades, type ÂÍÏÁ-10-630(400)/20 is intended for closing and opening energized sections of three-phase AC circuits of commercial frequency of 50 Hz and voltage rated at 10 kV. The isolators are mounted as completing items in package switch-gears (factory-assembled switch-gears), one-sided maintenance cells (KCO), package transformer substations and also for replacing load-breaking isolators of obsolete designs being currently in service.
| Parameters |
Values |
|
Rated voltage, kV
|
6-10 |
|
Maximum working voltage, kV
|
12 |
|
Rated current of main circuits, A
|
400; 630 |
|
Switch interrupting current rating, kA
|
20 |
|
Rated current of electrodynamic stability, kA
|
51 |
|
Mass, kg
|
29 |
|
Overall dimensions, mm
|
390x528x535 |
|
ambient air temperature: from - 400C to +400C
altitude above sea level: not exceeding 1000 m
working environment: explosion-proof
|